Elevator Fire Service And Smoke Testing in Oregon
If your building has a fire alarm, your elevator has to be tested regularly to prove it responds properly. We carry out the testing, fix what fails, and help you keep the records you are required to keep.

What Is Elevator Fire Service Testing?
Fire service testing checks that your elevator does the right thing when there is a fire in the building. It should stop taking normal calls, return to the ground floor, open its doors, and then wait to be taken over by the fire service.
That behavior is built into almost every commercial elevator. It is called firefighters' emergency operation, and like anything that only activates in an emergency, it can quietly stop working. Testing is how you find out it still does what it should.
If your elevator has a key switch in the lobby with a small fireman's helmet symbol next to it, your building has this system and it needs testing.
What Is the Difference Between Phase 1 and Phase 2?
The elevator recalls itself
When smoke is detected near the elevator, or when someone turns the lobby key switch, the elevator stops answering calls and returns to a designated floor. The doors open and stay open, and the car will not move.
The point is to stop people using the elevator during a fire. An elevator shaft carries smoke, and a car that stops on a burning floor opens its doors onto it.
The fire service takes control
Once the elevator has recalled, a firefighter can use a key inside the car to take manual control. Phase 2 lets them move the elevator to reach the fire, carry equipment up, or bring people down.
Phase 2 works differently from a normal elevator on purpose. Doors only close while the button is held, and the car only goes where the firefighter sends it. That is so nobody loses control of it in a burning building.
Both have to work. A test checks the recall in Phase 1 and at least one floor of movement in Phase 2.
How Often Does Fire Service Testing Need to Be Done?
Most owners are surprised there are two clocks running here, not one. The operation gets tested four times a year, the alarm devices behind it once a year.
Discuss Your Fire Service ScheduleQuarterly and Annual Testing Required
Oregon requires firefighters' emergency operation to be tested every calendar quarter, which works out to once every three months. Each test runs Phase 1 recall and at least one floor of Phase 2 movement.
On top of that, the Phase 1 fire alarm devices that trigger the recall, the smoke detectors wired to the elevator, must be tested once a year.
The results have to be written down and kept in a log on site. It is the requirement buildings most often fall behind on, because the quarterly clock is easy to lose track of.
Who does the testing?
The quarterly test is carried out by licensed elevator mechanics with the fire service key, and the record is kept on site. When something fails, it has to be corrected by a licensed elevator mechanic. We can do either part: perform the testing for you, or fix what your own testing finds.
Oregon Specifics
Oregon adopts the ASME A17.1 safety code but amends the fire service testing interval to quarterly. The national base code allows a monthly cycle, and some jurisdictions run monthly, but the Oregon requirement is every quarter with the alarm devices annually. Local fire authorities can set a stricter schedule than the state, so if you are unsure what applies to your building, call us and we will confirm it for your equipment and your area.

Smoke Detectors, Machine Rooms and Hoistway Access
Fire service does not work on its own. It depends on smoke detectors in the elevator lobbies, the machine room and sometimes the shaft itself, all wired to trigger the recall.
That means fire service testing sits between two trades. The detectors belong to your fire alarm contractor, the elevator response belongs to us, and a failure can sit on either side. A recall that does not happen might be a faulty detector or a fault in the elevator controller, and finding out which is part of the job. We also need access to the machine room and hoistway to test properly.
Book A Fire Test InspectionOther Testing Your Elevator Needs
Why Oregon Buildings Call Us for Fire Service Testing
Quarterly testing, annual alarm-device testing, who performs it, what has to be recorded. Most owners have never been told clearly, and it is the easiest requirement to fall behind on.

We tell you what to do.
We map out your testing frequency, who can perform each part, and exactly what has to be recorded.

We fix what fails.
A test that finds a fault needs a licensed elevator mechanic to correct it. We are that, which saves you a second call to a second company.
We work with fire contractors.
Recall problems sit between two systems. We work out which side the fault is on without pointing fingers.

We test older equipment.
Fire service on equipment installed decades ago behaves differently. We have seen most of it.
Fire Service Testing Across Oregon
We carry out fire service testing for buildings in all six regions.
Not sure if we reach you? Call us. We cover the whole state.
Fire Service Testing Questions
Fire service testing checks that an elevator responds correctly during a fire. It confirms Phase 1 emergency recall, where the elevator returns to a designated floor and stops taking calls, and Phase 2 emergency in-car operation, where a firefighter can take manual control of the car.

Ready to Talk Elevators?
Tell us what building you have and when fire service was last tested. We will tell you what is required and when we can be there. Four generations of Oregon elevators behind every answer.